DF6000 - USER MANUAL
34
Input/Outputs
Panel Inputs
Class Change: (option not required by EN54)
A pair of terminals are provided for class change. By shorting these terminals together (e.g. switch, time
clock) the alarm will sound (panel sounders + loop sounders only). The panel will not indicate a fire. The
alarm will cancel when the short circuit is removed. If the short circuit is not removed the alarms will not
cancel.
WARNING: No voltage should be applied to this input
Panel Outputs
Panel Sounders: (option 7.8 EN54 Pt 2)
Two pairs of outputs are provided. ONLY polarised equipment should be used. Ensure the polarity of the
connections are observed at all times and end of line resistors (6k8 5%) are fitted for correct operation.
The total alarm load across all sounder outputs = 1.5 Amp all outputs are fused with 1.6 Amp glass fuse
alarm devices should be spread equally across the 4 sounder circuits.
WARNING: Do not exceed the rated output current
Output Fire Alarm Routing Equipment
(option 7.9 EN54 Pt 2)
This output, which is fused and monitored using a 6.8k end of line resistor, is used for the automatic
transmission of the fire signals to fire alarm routing equipment (e.g. fire brigade). It operates by providing
12 V output to an auxiliary device (e.g. relay). It is current limited to 30 mA using a resettable polyswitch.
Class change and test conditions do not operate this output. If operated under a fire alarm condition, the
indication will be displayed on the touch screen display and will remain until the fire alarm is reset. Ensure
the polarity of the connections are observed at all times and end of line resistors (6k8 5%) are fitted for
correct operation.
Section 1 - System Installation and Design
class change
Switch/Contactorb timer etc.
(Apply NO voltage)
Both sounder circuits must
be terminated with a
6800 Ohm end of line resistor
All sounders must be polarised