DF6000 - USER MANUAL
36
Maintainance
Daily Inspection
Check that only the green “POWER ON” indicator shows. Inspect for any fault indication. Notify any faults
to a system supervisior.
Weekly Test
Check indicators. Press supervisor mode on the top left of the touch screen. Enter passcode. Select
“others” tab. Press the button labeled weekly test, confirm you wish to perform the test and the amber
“System Test” LED will light. The panel will stay in the weekly test mode for 5mins before resetting. During
the weekly test, trigger a smoke detector or callpoint and check the fire panel registers the device and
illuminates the correct zonal indicator. Trigger a different device every time a weekly test is performed
ensuring devices are tested in rotation until all have been checked. It is advisable to develop a detailed a
building plan highlighting devices and locations to aid testing. The panel will reset automatically once the
5mins have elapsed. If no devices are triggered during the weekly test the panel will abort the test and
reset after 5mins. Record weekly test in the table provided in the log book.
Quarterly Test
Check all previous log book entries and verify that remedial action has been taken. Carry out the weekly
test. Visually examine the batteries and their connections, by loosening the screws behind printer door
and opening the hinged front from the right hand side. Disconnect the mains supply and check that the
batterry is capable of supplying the alarm sounders, by operating a callpoint.
Annual Test
As weekly test and quarterly test above. Additionally test all sensors and callpoints and check operation.
Every 2-3 Years
Replace or return the smoke detectors for cleaning to ensure correct operation and freedom from false
alarms. Special equipment is required for cleaning smoke detectors. Consult Cooper Lighting and Safety.
Every 5 Years
Replace sealed lead acid battery.
Cleaning
When cleaning the panel, use a moist cloth. Do not use solvents or harsh abrasives.
Printer Paper Order Code
Servicing: Cooper Lighting and Safety can offer a regular servicing contract.
Cooper Lighting and Safety
Service Division,
Wheatley Hall road
Doncaster
DN2 4NB.
Telephone: 01302 303352 Web: www.cooperfire.com