Code UCPD-2W UCPT-2W UCHT-2W UCHTI-2W UCHR-2W UCHRI-2W
Description Conventional Detector Conventional Detector Conventional Detector Conventional Detector Conventional Detector Conventional Detector
Optical, 2 Wire Opto-Heat, 2 Wire Fixed Heat, 135ºF, 2 Wire Fixed Heat, 194ºF, 2 Wire Rate of Rise & Fixed Heat Rate of Rise & Fixed Heat
135ºF, 2 Wire 194ºF, 2 Wire
Standards UL268 UL268 UL521 UL251 UL251 UL251
Supply Ratings
Working Voltage 15 V dc to 30 V dc 15 V dc to 30 V dc 15 V dc to 30 V dc 15 V dc to 30 V dc 15 V dc to 30 V dc 15 V dc to 30 V dc
Voltage Waveform Filtered dc +/- 1 V (max), Filtered dc +/- 1 V (max), Filtered dc +/- 1 V (max), Filtered dc +/- 1 V (max), Filtered dc +/- 1 V (max), Filtered dc +/- 1 V (max),
ripple @120Hz ripple @120Hz ripple @120Hz ripple @120Hz ripple @120Hz ripple @120Hz
Standby Current 95 μA (average) 95 μA (average) 70 μA (average) 70 μA (average) 70 μA (average) 70 μA (average)
Alarm Current must be held externally to must be held externally to must be held externally to must be held externally to must be held externally to must be held externally to
40 mA (max) 40 mA (max) 40 mA (max) 40 mA (max) 40 mA (max) 40 mA (max)
Surge Current 340 μA (max) 340 μA (max) 340 μA (max) 340 μA (max) 340 μA (max) 340 μA (max)
Timings
Start-up Time 20 seconds 20 seconds 20 seconds 20 seconds 20 seconds 20 seconds
Reset Time 2 seconds (max) 2 seconds (max) 2 seconds (max) 2 seconds (max) 2 seconds (max) 2 seconds (max)
Sensitivity
Sensitivity 2.55+/- 0.33%/ft 2.55+/- 0.33%/ft N/A N/A N/A N/A
Sensitivity Checker Use No-Climb, TRUTEST, Use No-Climb, TRUTEST, Use No-Climb, TRUTEST, Use No-Climb, TRUTEST, Use No-Climb, TRUTEST, Use No-Climb, TRUTEST,
UL Listing 77TL UL Listing 77TL UL Listing 77TL UL Listing 77TL UL Listing 77TL UL Listing 77TL
Heat Class
Heat Element Rating N/A 135ºF 135ºF 194ºF 135ºF 194ºF
Heat Detector Spacing N/A 50ft (heat alone operation) 50ft 50ft 50ft 50ft
Mounting Position Ceiling in open areas Ceiling in open areas Ceiling in open areas Ceiling in open areas Ceiling in open areas Ceiling in open areas
Environmental
Operating Temperature 32ºF to 100ºF 32ºF to 100ºF 32ºF to 100ºF 32ºF to 150ºF 32ºF to 150ºF 32ºF to 150ºF
Mounting Position Ceiling in open areas Ceiling in open areas Ceiling in open areas Ceiling in open areas Ceiling in open areas Ceiling in open areas
Compatibility
Compatibility Indentifier W001 W001 W001 W001 W001 W001
Compatible Bases CB or CB2E CB or CB2E CB or CB2E CB or CB2E CB or CB2E CB or CB2E
Suitable for use with Menvier UL fire systems Menvier UL fire systems Menvier UL fire systems Menvier UL fire systems Menvier UL fire systems Menvier UL fire systems
Technical Specification
Code Description
UCPTR-4W 4 Wire Detector
UCPD-2W 2 Wire Detector, Optical
UCPT-2W 2 Wire Detector, Opto-Heat
UCHT-2W 2 Wire Detector, Fixed Heat 135°F
UCHTI-2W 2 Wire Detector, Fixed Heat 194°F
UCHR-2W 2 Wire Detector. Rate of Rise and Fixed Heat 135°F
UCHRI-2W 2 Wire Detector, Rate of Rise and Fixed Heat 194°F
Product Codes
Dimensions
Dia
D
Description Dia (mm) D (excl base) D (incl base)
Optical 101 33 45
Opto-Heat 101 43 55
Multi-Mode Heat 101 43 55
Conventional Detectors