Note:
1. The end of line resistor must always be fitted, even
if the inputs are unused.
2. Recommended cable type FPLP (plenum cable),
type FPLR (riser cable), or type FPL.
Description SLC Field Callpoint Detector Sounder 1 24 V External External
Wiring (Input) Zone Zone Sounder 2 Supply PSU Monitor
Wiring 12 12 12 12 12 12
Gauge Max AWG Max AWG Max AWG Max AWG Max AWG Max AWG
Wiring Class A Class B Class B Class B N/A N/A
Class Style 7 Style C Style C Style Y
Ground 0.1 ohm 0.1 ohm 0.1 ohm 0.1 ohm TBD TBD
Fault Power Power
Impedance Supply Supply
Supervised, Yes Yes Yes Regulated Supervised Supplementary
Power Supervised Power
Limited Power Limited
Limited
Compatibility ULCV1 Compatible Detectors: UPCD-2W, UCPT-2W, UCHRI, UCHT, UCHTI
Identifier
Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries
in the surface mounting back-box.
3. Fit the back-box in position and pass the wires
into it.
4. Connect the unit according to the diagram below.
Note:
No addressing of the interface is required.
(See control panel operation for details).
Standard Connections
Technical Specification
Operation
Callpoint Zone:
Normal Standby, Alarm, NAC Silenced, Alarm Reset,
Trouble, Supervisory, Drill.
Detector Zone:
Normal Standby, Alarm, Trouble.
Code ULCSUM355
Description Shop Mointor Unit
Standards UL864 9
th
edition
Signalling Line Circuit
Style 7, Class A, Supervised, Power Limited
Voltage 24 V dc
Current 4.9 mA to 5.0 mA
Line Impedance 50 Ω (max)
Detector Zone
Style C, Class B, Supervised, Power Limited
Voltage 21 V dc to 26 V dc, 22.9 V dc (nom)
Current (Alarm) 17 mA to 40 mA
Line Impedance 2.5 Ω (max)
End of Line Resistor 5.6 kΩ
Fire Input Trigger 680 Ω
UPCD-2W, UCPT-2W, UCHRI, UCHT
any combination thereof
Compatibility Identifier ULCV1
Sounder 1, Sounder 2
Style Y, Class B, Supervised, Power Limited
Voltage 24 V dc
Current 1 A (max)
Line Impedance 8 Ω
End of Line Resistance 12 kΩ
Callpoint Zone
Style C, Class B, Supervised, Power Limited
Voltage
(8.4 Vpp pulsed every 1 second) 8.4 V
Current 1.2 mA
Line Impedance 16 Ω
End of Line Resistor 6.8 kΩ
Trigger Resistor 680 Ω
24 V external PSU
Supervised, Power Limited
Voltage 24 V dc
Current 2 A (max)
End of Line Resistor 12 kΩ
Line Impendance 4 Ω
Gauge Wire 12 AWG
UL 1481 listed regulated for fire, current limited
Environmental
Operating Temperature 0°C to 49°C
Humidity (Non Condensing) 0 to 93 %RH
Physical
Dimensions (H x W x D) 180mm x 129mm x 60mm
Weight 0.28kg
Ingress Protection IP65
Compatibility
Suitable for use with Menvier analogue addressable fire systems
Code Description
ULCSUM355 Shop Monitor Unit
Product Codes
LOOP
OUT
IN
SOUNDER
EXTERNAL
PSU
MONITOR
24V
EXTERNAL
PSU
INPUT
1
2
Fault
Contact
N/O
UL1481 LISTED FOR FIRE
24V DC OUTPUT
POWER SUPPL Y UNIT
24V
O/P
-
-
+
+
+
+
-
-
+
+
+
+
-
-
-
-
12K
12K
12K
Addressable Loop
CALL
POINT
ZONE
DETECT OR
ZONE
--
++
- OUT +
- IN +
- OUT +
- IN +
6K8
5K6
Maximum 20
Conventional
Detectors
FIRE
RELAY
NC
ULCSUM355 - Shop Monitor Unit
Dimensions
W
H
D
H (mm) W (mm) D (mm)
180 129 60